Fault
E1 Internal Temperature Sensor Error
LED
What it means
The main control panel in the indoor unit detected a short circuit or open circuit condition on the internal temperature sensor.
Special attention
Standard resistance for most inverter model internal temperature sensors is 15KΩ at 25°C. Using an incorrect sensor causes wrong temperature readings. To verify sensor accuracy, switch to Blowing mode and compare the screen temperature display against a thermometer. A sensor with resistance above 15KΩ causes the unit to read temperature as lower than actual — possible symptom: heating-mode shutdown or cooling-mode startup failure. A sensor with resistance below 15KΩ causes the unit to read temperature as higher than actual — possible symptom: heating-mode startup failure or cooling-mode shutdown.
Inspection path
1 Sensor → 2 Sensor wire → 3 Connectors → 4 Main internal control panel
Diagnostic procedure
- Measure sensor resistance. For inverter models it should be approximately 15KΩ at 25°C. Check for short circuit or open circuit.
- Inspect the sensor wire for breaks or damage.
- Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel. Gently tug the terminal if needed.
- Check whether the sensor has moisture damage.
- If no standard sensor is available, swap in a nearby sensor temporarily. If the error clears, replace the original sensor. If the error persists, inspect and potentially replace the main internal control panel.
Tools
- Multimeter
- 15KΩ standard sensor (25°C)
Frequent parts
- Internal temperature sensor
- Main internal control panel
Sensors referenced
Safety
Disconnect power at the breaker before opening any access panel. DC bus capacitors
retain charge for up to 5 minutes after disconnect - verify with a meter before
touching live components.