Knowledge Base

Error Codes

Fault, protection, and function-prompt codes

Fault Codes

Fault

E0

Overcurrent Protection of Indoor Unit

Wall MountedFloor Standing DRAFT

The main control panel detects that the system's working current has exceeded the upper protection limit. The unit stops running and displays E0.

Inspection Path Current transformer Power line Compressor line Connector assembly
Tools
Current clampMultimeter
Frequent Parts
Indoor unit main control panelPower lineCompressor
  1. For fixed-frequency models: confirm the live wire passes through the current transformer correctly. If not, reroute the wire and reboot.
  2. Use a current clamp to measure working current and compare against the nameplate range. If current is within range, the current transformer itself may be faulty — replace the indoor unit main control panel.
  3. Measure supply voltage and confirm it falls within the normal operating range. If abnormal, investigate local grid stability.
  4. If working current exceeds the nameplate range and supply voltage is normal, the system may be blocked or the unit overloaded. Inspect based on actual site conditions.
E1

Internal Temperature Sensor Error

Wall MountedFloor StandingMobile DRAFT

The main control panel in the indoor unit detected a short circuit or open circuit condition on the internal temperature sensor.

LED Pattern ● ★ ●
Inspection Path Sensor Sensor wire Connectors Main internal control panel
Tools
Multimeter15KΩ standard sensor (25°C)
Frequent Parts
Internal temperature sensorMain internal control panel
Sensors Required
  • Internal temperature (15 kΩ @ 25°C)
  1. Measure sensor resistance. For inverter models it should be approximately 15KΩ at 25°C. Check for short circuit or open circuit.
  2. Inspect the sensor wire for breaks or damage.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel. Gently tug the terminal if needed.
  4. Check whether the sensor has moisture damage.
  5. If no standard sensor is available, swap in a nearby sensor temporarily. If the error clears, replace the original sensor. If the error persists, inspect and potentially replace the main internal control panel.
Special Attention: Standard resistance for most inverter model internal temperature sensors is 15KΩ at 25°C. Using an incorrect sensor causes wrong temperature readings. To verify sensor accuracy, switch to Blowing mode and compare the screen temperature display against a thermometer. A sensor with resistance above 15KΩ causes the unit to read temperature as lower than actual — possible symptom: heating-mode shutdown or cooling-mode startup failure. A sensor with resistance below 15KΩ causes the unit to read temperature as higher than actual — possible symptom: heating-mode startup failure or cooling-mode shutdown.
E2

External Coil Sensor Error

Wall MountedFloor Standing DRAFT

The main external control panel detected a short circuit or open circuit condition on the external coil sensor.

LED Pattern ● ★ ★
Inspection Path Sensor Sensor wire Connectors Main external control panel
Tools
Multimeter20KΩ standard sensor (25°C)
Frequent Parts
External coil sensorMain external control panel
Sensors Required
  • External coil (20 kΩ @ 25°C)
  1. Measure sensor resistance. For inverter models it should be approximately 20KΩ at 25°C. Check for short circuit or open circuit.
  2. Inspect the sensor wire for breaks or damage.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel.
  4. Check whether the sensor has moisture damage. Coil sensors are especially susceptible to moisture when the sensor lead runs above the copper pipe.
  5. If no standard sensor is available, swap in a nearby sensor temporarily. If the error clears, replace the original sensor. If the error persists, inspect and potentially replace the main external control panel.
Special Attention: Standard resistance for most inverter model external coil sensors is 20KΩ at 25°C. A sensor with resistance above 20KΩ causes the unit to read coil temperature as lower than actual — possible symptoms: frequent defrost cycles, illusory defrosting, or protection errors during cooling. A sensor with resistance below 20KΩ causes the unit to read coil temperature as higher than actual — possible symptoms: defrost failures during heating or protection activation during cooling.
E3

Internal Coil Sensor Error

Wall MountedFloor StandingMobile DRAFT

The main internal control panel detected a short circuit or open circuit condition on the internal coil sensor.

LED Pattern ● ★ ○
Inspection Path Sensor Sensor wire Connectors Main internal control panel
Tools
Multimeter5KΩ or 20KΩ standard sensor (25°C)
Frequent Parts
Internal coil sensorMain internal control panel
Sensors Required
  • Internal coil (20 kΩ @ 25°C)
  1. Measure sensor resistance. For inverter models it should be approximately 20KΩ at 25°C. Check for short circuit or open circuit.
  2. Inspect the sensor wire for breaks or damage.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel.
  4. Check whether the sensor has moisture damage. Coil sensors are especially susceptible to moisture when the sensor lead runs above the copper pipe.
  5. If no standard sensor is available, swap in a nearby sensor temporarily. If the error clears, replace the original sensor. If the error persists, inspect and potentially replace the main internal control panel.
Special Attention: Standard resistance for most inverter model internal coil sensors is 20KΩ at 25°C. Using an incorrect sensor can trigger anti-freezing or overheat protection. A sensor with resistance above 20KΩ reads coil temperature as lower than actual — possible symptoms: high-pressure cold-blast protection during heating or frequent anti-freezing protection during cooling. A sensor with resistance below 20KΩ reads coil temperature as higher than actual — possible symptoms: frequent overheat protection during heating or overload protection during cooling.
E4

Internal Fan Error / Sliding Door Error

Wall MountedFloor StandingMobile

For wall-mounted PG motor models: the main internal control panel is not receiving the speed feedback signal from the PG motor. For wall-mounted and mobile DC motor models: the main internal control panel cannot receive rotational speed feedback through the DC motor's green plug connection. For floor standing sliding door models: the upper or lower photoelectric switch cannot sense the sliding door position normally. In all cases, primary causes are mechanical jam, a damaged speed feedback component, or a fault in the main internal control panel's receiving circuit.

LED Pattern ○ ★ ●
Inspection Path Fan or sliding plate for mechanical jam Speed feedback line or motor terminal connectors Speed feedback terminal connector on control panel Main internal control panel
Tools
MultimeterPG motor in working condition (PG motor models)DC motor in working condition (DC motor models)Photoelectric switch in working condition (floor standing only)
Frequent Parts
Indoor fan (mechanical jam)PG motorDC motorMain internal control panelPhotoelectric switch (floor standing only)Reversible synchronous motor (floor standing only)
  1. Check whether the fan can run for a period before the error appears. If so, mechanical jam can be excluded as the cause.
  2. Disconnect power and manually rotate the indoor fan blade to check for any resistance. Occasional fan errors may be related to bearing issues.
  3. For PG motor models: reconnect the drive wire and speed feedback wire to rule out connector loosening. For DC motor models: unplug and reseat the DC motor terminal connector.
  4. Check that the speed feedback plug-in terminal on the control panel is firmly seated. Gently tug if needed.
  5. For DC motor models: with the unit powering on in cooling mode, monitor voltage between the second (yellow) and fourth (black) wires of the DC motor terminal. Voltage should rise gradually and the motor should begin accelerating. If the motor does not rotate, the DC motor is damaged.
  6. Swap in a known-good motor (without mounting it to the fan assembly). If the error persists, replace the main internal control panel. If the error clears, replace the motor.
  7. For floor standing sliding door models: observe whether the sliding plate jams during startup or shutdown. If the door moves normally but the error persists, check the photoelectric switches. Verify the reversible synchronous motor is receiving 220V. Replace the faulty switch with a new sealed unit and confirm correct terminal color orientation — upper and lower photoelectric switches have different colored connectors and must not be swapped.
Special Attention: The main internal control panel will not report a fan error while the fan is still rotating. Errors may go unreported even when obvious fan problems exist (such as low-speed rotation from damaged capacitors or uneven speed from abnormal feedback). For 3-core DC motor models: before startup, the fan blades will mechanically shake for 3–5 seconds during the blade position locking phase — this is normal and not a fault. For floor standing sliding door models: new machines may have the sliding plate secured with tape — remove before testing.
E5

Indoor and Outdoor Unit Communication Error

Wall MountedFloor Standing

The frequency converter requires continuous communication between the indoor and outdoor units. When this communication cannot be established, both units indicate this error. Note: external unit power failures or other external errors can also trigger this code — distinguish pure communication failure from an external unit startup failure before diagnosing. Alternate display on some models: 5E.

LED Pattern ★ ● ●
Inspection Path Confirm whether the outdoor unit can power on (indicator lights on then off, relay picks up, PTC does not heat significantly) Verify indoor and outdoor unit compatibility and wire phase sequence Connecting wire contact quality Main internal control panel Main external control panel
Tools
MultimeterMain internal control panel in normal working condition
Frequent Parts
Connecting wire phase sequence and contactMain internal control panelMain external control panelModule panel
  1. Confirm that the indoor and outdoor units are correctly matched and connected. Power on and observe the outdoor unit — three indicator lights should illuminate then go off and the relay should pull in. If not, investigate the power supply path.
  2. Verify the live and neutral wires of the indoor and outdoor units are connected to their matching counterparts. Check that the connecting wires are making solid contact.
  3. Connect the black signal line S to terminal N of the outdoor unit. Power on — if E5 persists, the main external control panel may need replacement. If E5 clears, the signal connection was the issue.
  4. If E5 still persists after step 3, replace the main internal control panel. If the error remains, replace the main external control panel.
Special Attention: When the outdoor unit cannot power on: if the indoor terminal board is not transmitting 220V, replace the main internal control panel. If 220V is present at the outdoor terminal board, check the fuse, reactor, and bridge rectifier. If those are normal, try disconnecting weak-current data wires between control boards — if the main external control panel then initializes successfully, the module panel is likely faulty. If the main external control panel still fails to initialize, replace it.
E8

Communication Failure Between Display Board and Main Control Panel

Floor StandingMobile DRAFT

Floor standing and mobile units require communication between the display board and the indoor unit main control panel. When this connection is interrupted, the display board reports this error. Only three components are involved: the main internal control panel, the connection line, and the display board.

Inspection Path Connection line between display board and main control panel Display board Main internal control panel
Tools
MultimeterKnown-good main internal control panelKnown-good display board
Frequent Parts
Main internal control panelDisplay boardConnection line
  1. Check that the connection line between the display board and main control panel is fully seated and undamaged. Re-seat or replace as needed.
  2. Replace with a known-good main internal control panel. If E8 clears after rebooting, the original control panel is faulty. If E8 persists, the display board is faulty — replace it.
  3. If replacing either component individually does not resolve the error, the display board and control panel may be incompatible with each other — replace both simultaneously.
Special Attention: When replacing either the display board or the main internal control panel, confirm they are compatible. If compatibility cannot be confirmed, replace both together.
Eb

Indoor EE Failure

Wall MountedFloor Standing DRAFT

The indoor unit stores operating parameters in an 8-pin EEPROM chip (EE). The main control panel motor can only run after reading this data. If the data cannot be read, this failure is indicated. Possible causes: incorrect EE chip data format; damaged EE chip; poor contact of EE chip or fault in the EE reading circuit; EE chip installed backwards.

Inspection Path Internal main control panel
Frequent Parts
EE chip contactInternal main control panel
  1. Replace the internal main control panel directly.
F0

External DC Fan Error (3-Core Terminal Motor)

Wall MountedFloor Standing DRAFT

The frequency-converting outdoor unit uses a 3-lead-wire externally driven DC motor (used after 2012). It has no speed feedback circuit — the main control panel drives it directly and monitors current balance across the three lead wires. When the panel detects imbalanced current on those wires, it indicates this error.

LED Pattern ★ ○ ○
Inspection Path Mechanical jam of external fan blades Motor terminal connectors and wire order Main external control panel External DC motor
Tools
Main external control panel in normal working condition
Frequent Parts
Mechanical jam of external fanMain external control panelExternal DC motor
  1. Confirm there is no mechanical jam in the external fan blades.
  2. Verify the motor terminal is firmly connected and the wire order is correct. If the fan on a newly installed unit rotates in reverse, confirm the color order of the three lead wires or swap any two of the three motor wires to correct rotation direction.
  3. This 3-core DC motor scheme is reliable, so the drive section of the main external control panel is the more likely failure point. Replace the main external control panel with a matched unit. If the fan returns to normal, the original control panel is faulty. If the error persists, replace the external DC motor.
Special Attention: Unlike 5-core internal DC motors, the 3-core external DC motor goes through a blade position locking phase before startup: the blades will mechanically shake for 3–5 seconds, then begin rotating slowly. This is normal behavior — do not diagnose it as a fault.
F1

Module Protection Error

Wall MountedFloor Standing DRAFT

The power module directly drives the compressor. When it detects overcurrent, overvoltage, or overheat, it stops the compressor and sends a shutdown request to the module panel. The resulting error is called module protection error. L-codes (L0–LC) are subdivided failures of F1 — see those entries for specific subcategory names and primary parts.

LED Pattern ★ ★ ●
Inspection Path Supply voltage Compressor wire and reactor wire System pressure Module panel Main external control panel Compressor
Tools
MultimeterPressure gaugeMegameterModule panel in normal working condition
Frequent Parts
Supply voltageCompressor wireReactorModule panelMain external control panelCompressor
  1. Check if the compressor wire order is correct. If wired in reverse, try swapping the U-V phase wires to see if the error clears.
  2. Verify supply voltage stability. Measure system pressure — high pressure can cause compressor rotation problems.
  3. Confirm the module panel is firmly mounted to the radiator for adequate cooling. Check if indoor or outdoor heat exchangers are dirty, which causes poor heat transfer and elevated system pressure.
  4. If the error appears immediately on startup, a physical component failure is likely (unrelated to voltage or pressure). Inspect for strike-arc damage near the module panel. Use a multimeter to confirm equal resistance between any two compressor wires — should be ohm-level and equal across all pairs. Use a megameter to verify insulation resistance of each compressor wire to earth (should be MΩ level). Check that the reactor wire is firmly connected and the reactor is not damaged.
  5. Test that the 15V and 5V (or 3.3V) power supplies on the module panel are stable. Rule out power supply issues originating from the main external control panel.
  6. Using the diode function on the multimeter, test the power module: measure P against U, V, and W — one direction should show infinite resistance, the other a fixed on-state voltage (typically ~0.5V). Repeat for N against U, V, and W. A short circuit in any measurement indicates a damaged power module.
  7. Replace the module panel with a known-good unit. If the unit runs normally after replacement, the original module panel is damaged.
  8. After ruling out module, wiring, system, and power supply issues, listen to the compressor. If only electromagnetic sound is present without the compressor starting, or if the compressor runs irregularly then shuts down and indicates error, the compressor may be blocked or damaged.

See also: F3

F2

PFC Protection Error

Wall MountedFloor Standing DRAFT

The PFC board performs power factor correction and voltage boosting in inverter units. When it cannot complete power calibration due to overcurrent or overvoltage, it indicates this error. Depending on the model, PFC function may be integrated into the module panel or main control panel rather than a separate board.

LED Pattern ★ ★ ○
Inspection Path Supply voltage AC and DC power path PFC board data wire PFC board Main external control panel
Tools
MultimeterPFC board in normal working condition
Frequent Parts
Supply voltageReactorPFC boardModule panelMain external control panel
  1. Check if supply voltage is unstable or too low (below AC 135V).
  2. The reactor is a core PFC component. Check if the reactor itself is damaged or if the reactor connecting wire has poor contact. Never remove the reactor and replace with a short circuit.
  3. If the error appears immediately on startup, inspect for strike-arc damage near the module panel — a physical failure is likely.
  4. Test that the 15V and 5V (or 3.3V) power supply on the PFC board is stable. Rule out control power issues originating from the main external control panel.
  5. Replace the PFC board with a known-good unit. If the unit runs normally after replacement, the original PFC board is damaged.
  6. Note: main external control panel power supply problems can also cause PFC board failures. Rule this out if PFC board replacement does not resolve the issue.
  7. For models where PFC and compressor drive are integrated into a single module panel, replace the integrated panel.
  8. For single-panel single-chip controllers: if PFC protection error appears with no voltage, reactor, or reactor wiring issues, replace the external unit controller directly.
F3

Compressor Out-of-Step Error

Wall MountedFloor Standing DRAFT

The module panel monitors current on the compressor lead wires and calculates rotor position during operation. When the compressor deviates far from normal status — due to excessive current or inability to detect rotor position — this error is indicated. It frequently follows F1 (Module Protection Error) and shares a similar diagnostic approach.

LED Pattern ★ ● ★
Inspection Path Supply voltage Compressor wire and reactor wire System pressure Module panel Main external control panel Compressor
Tools
MultimeterPressure gaugeModule panel in normal working condition
Frequent Parts
Supply voltageCompressor wireReactorModule panelMain external control panelCompressor
  1. Check if the compressor wire order is correct. If reversed, try swapping the U-V phase wires.
  2. Verify supply voltage stability. Measure system pressure — high pressure causes compressor rotation problems.
  3. Confirm the module panel is firmly mounted to the radiator. Check if heat exchangers are dirty, causing elevated system pressure.
  4. If the error appears immediately on startup, inspect for strike-arc damage. Verify equal resistance between any two compressor wires (ohm-level, equal across all pairs). Verify insulation resistance of each compressor wire to earth (MΩ level). Also check whether DC voltage between P and N is too high (above 200V). Confirm the reactor wire is sound.
  5. Test that the 15V and 5V (or 3.3V) power supplies on the module panel are stable.
  6. Replace the module panel with a known-good unit. If the unit runs normally after replacement, the original module panel is damaged.
  7. After ruling out module, wiring, system, and power supply issues, listen to the compressor. If only electromagnetic sound is present without startup, or if the compressor runs irregularly before shutdown, the compressor may be blocked or damaged.
Special Attention: F3 (compressor out-of-step) and F1 (module protection) are both abnormal compressor operating conditions — F3 is calculated by the module panel's main chip, while F1 is detected by the power module itself. When diagnosis is uncertain for either, analyze both errors together using the same method. For inverter units in poor electrical environments or older units, occasional occurrences of these errors represent normal protection behavior.

See also: F1

F4

Exhaust Sensor Error

Wall MountedFloor Standing DRAFT

The main external control panel detected a short circuit or open circuit condition on the exhaust sensor.

LED Pattern ★ ○ ★
Inspection Path Exhaust sensor Sensor wire Connectors Main external control panel
Tools
Multimeter50KΩ standard exhaust sensor (25°C)
Frequent Parts
Exhaust sensorMain external control panel
Sensors Required
  • Exhaust (50 kΩ @ 25°C)
  1. Measure sensor resistance. With the compressor off, resistance should be approximately 50KΩ at 25°C. After the compressor runs for a period, resistance should be between 3KΩ and 30KΩ (corresponding to 100°C–38°C exhaust temperature). Check for short circuit or open circuit.
  2. Inspect the sensor wire and connecting wire for damage.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel.
  4. Check whether the sensor has moisture damage, especially if the sensor lead runs above the copper pipe.
  5. If no standard sensor is available, swap with an adjacent sensor and observe whether the error changes to a different sensor error. If so, the exhaust sensor is faulty — replace it. If the original error persists, replace the main external control panel.
Special Attention: Standard resistance for most exhaust sensors is 50KΩ at 25°C. Installing an incorrect sensor causes mistaken exhaust temperature readings and frequent protection activation. For example, a 20KΩ coil sensor installed in place of the exhaust sensor will cause the controller to read exhaust temperature as higher than actual, triggering frequent high exhaust temperature protection and compressor shutdowns. Note: some models may display this error as LED pattern ● ● ○ (LED1 on, LED2 on, LED3 off) in addition to ★ ○ ★ — both indicate the same fault.
F5

Compressor Top Head Sensor Error

Wall MountedFloor Standing DRAFT

The compressor top head sensor is typically a temperature protection switch that remains closed (short circuit) under normal temperature and opens (open circuit) when temperature is too high. The main external control panel indicates this error when it detects disconnection of this switch.

LED Pattern ● ● ★
Inspection Path Compressor top head temperature (check if genuinely above 110°C) Compressor top head sensor (temperature protection switch) Sensor wire Connectors Main external control panel
Tools
Pressure gaugeMultimeter
Frequent Parts
System pressureRefrigerant level (liquid shortage)Compressor top head sensor (temperature protection switch)Main external control panel
  1. First check if the compressor top head temperature is genuinely too high (above 110°C), which would trigger the protection switch. Common causes: refrigerant shortage causing the compressor to idle, or system blockage creating excessive pressure.
  2. After ruling out system issues, test the sensor terminals with a multimeter. The temperature protection switch is normally closed — an open circuit indicates a sensor or lead wire problem.
  3. Inspect the sensor wire and connecting wire for damage.
  4. Verify all terminal connectors are firmly seated.
  5. Disconnect power and use a metal conductor to short-circuit the compressor top head terminal on the main external control panel. If the error disappears after restarting, replace the sensor. If the error persists, replace the main external control panel.
Special Attention: The compressor top head sensor is a simple, reliable temperature switch and rarely fails on its own. Direct diagnostic attention to system pressure and actual compressor temperature before assuming sensor failure. Note: LED pattern ○ ● ○ (LED1 off, LED2 on, LED3 off) also indicates compressor shell temperature protection and is diagnosed using the same procedure as F5.
F6

External Temperature Sensor Error

Wall MountedFloor Standing DRAFT

The main external control panel detected a short circuit or open circuit condition on the external temperature sensor.

LED Pattern ○ ★ ★
Inspection Path Sensor Sensor wire Connectors Main external control panel
Tools
Multimeter15KΩ standard sensor (25°C)
Frequent Parts
External temperature sensorMain external control panel
Sensors Required
  • External temperature (15 kΩ @ 25°C)
  1. Measure sensor resistance. It should be approximately 15KΩ at 25°C. Check for short circuit or open circuit.
  2. Inspect the sensor wire for breaks or damage.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints between the terminal and the main control panel.
  4. Check whether the sensor has moisture damage.
  5. If no standard sensor is available, swap in a nearby sensor temporarily. If the error clears, replace the original sensor. If the error persists, replace the main external control panel.
Special Attention: Standard resistance for most external temperature sensors is 15KΩ at 25°C. Sensor resistance decreases as temperature increases and increases as temperature decreases. Using an incorrect sensor causes wrong outdoor temperature readings and incorrect control decisions.
F7

OVP or UVP Error (Over/Under Voltage Protection)

Wall MountedFloor Standing DRAFT

All inverter units include voltage inspection circuits (located on the module panel or main external control panel depending on model). When supply voltage drops below 135V or exceeds 275V, the inspection circuit detects over or under voltage and the main external control panel raises this alarm.

LED Pattern ○ ○ ●
Inspection Path Supply voltage Internal DC voltage Reactor wiring Module panel Main external control panel
Tools
Multimeter
Frequent Parts
Supply voltageReactorModule panelMain external control panel
  1. Check the supply environment while the compressor is running. Normal operating voltage is 198–242V; the minimum guaranteed operating range is 165–265V. If voltage drops by more than 25V after the compressor starts, the supply line has insufficient capacity — advise the user to upgrade the circuit or install a dedicated voltage stabilizer.
  2. For outdoor units with PFC panels (without separate rectifier bridges): measure DC voltage between P and N on the module panel while the compressor runs. Voltage should be above 200V. If below this threshold, the reactor may be faulty or the PFC broken.
  3. If the compressor is not running but the error is reported and measured supply voltage is above 150V, the voltage inspection circuit itself may be faulty. Identify which control panel hosts the circuit (module panel for two-panel units; external controller for single-panel units) and replace it.
Special Attention: On some models, the OVP/UVP signal is transmitted through the connector between the module panel and main external control panel. A poor connection here may cause the signal to fail to transmit, resulting in a false alarm that may eventually resolve as F8 (module-to-controller communication error). Note this distinction during diagnosis.

See also: F8

F8

Main External Control Panel and Module Panel Communication Error

Wall MountedFloor Standing DRAFT

Applies only to models where the module panel is physically separate from the main external control panel. When communication between them is interrupted during operation, this error is raised. Only three components are involved: the module panel, the data connection line, and the main external control panel.

LED Pattern ★ ● ○
Inspection Path Data line connection between module panel and main control panel Module panel power supply Module panel Main external control panel
Tools
MultimeterModule panel in normal working condition
Frequent Parts
Module-to-main control data lineModule panelMain external control panel
  1. Check that the communication connection line (typically a 4-chip connector) between the module panel and main control panel is fully seated and undamaged.
  2. Use a multimeter to verify that the main external control panel is delivering correct power to the module panel. Specifically confirm that 5V (or 3.3V) is present at the module panel input.
  3. Replace the module panel with a known-good unit. If the error clears on startup, the original module panel is faulty. If the error persists, replace the main external control panel.

See also: F7

F9

Outdoor EE Error

Wall MountedFloor Standing DRAFT

The outdoor unit stores operating parameters in an 8-pin EEPROM chip (EE). The main external control panel motor can only run after reading this data. If the data cannot be read, this error is raised. Possible causes: incorrect EE chip data format; damaged EE chip; poor contact of EE chip or fault in the EE reading circuit; EE chip installed backwards.

LED Pattern ★ ○ ●
Inspection Path Main external control panel
Frequent Parts
EE chip contactMain external control panel
  1. Replace the main external control panel directly.
FA

Recirculated Sensor Error

Wall MountedFloor Standing DRAFT

Applies only to models with electronic expansion valves. The recirculated sensor back temperature is used for electronic expansion valve adjustment and to confirm the four-way valve has changed position during heating. When the main control panel detects an open circuit or short circuit on this sensor, it raises this error.

LED Pattern ● ○ ★
Inspection Path Four-way valve Recirculated sensor Sensor wire Connectors Main external control panel
Tools
MultimeterPressure gauge20KΩ recirculated sensor in normal working condition
Frequent Parts
Four-way valveRecirculated sensorMain external control panel
Sensors Required
  • Recirculated (20 kΩ @ 25°C)
  1. If the error appears in heating mode but not cooling mode, first check whether the four-way valve failed to change position or is experiencing backflow — estimate via high and low pressure readings. For electrical confirmation during heating: verify the four-way valve terminal switches a 220V circuit. If 220V is present but the valve still fails to change position, the four-way valve is faulty. If 220V is absent in heating mode, the main external control panel is faulty.
  2. If the four-way valve is not the issue, measure sensor resistance (should be approximately 20KΩ at 25°C). Check for short circuit or open circuit.
  3. Verify all terminal connectors are firmly seated. Check for loose solder joints.
  4. Check whether the sensor has moisture damage, especially if the sensor lead is routed above the copper pipe.
  5. Replace the suspect recirculated sensor with a known-good unit. If the error clears, the original sensor is faulty. If the error persists, replace the main external control panel.
Fb

Cabinet Internal Fan Error

Wall MountedFloor Standing DRAFT
Redirects to: E4 - see that entry for the full troubleshooting procedure.
L0

DC Over/Under-Voltage Failure

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower grid
L1

Overcurrent Protection on Phase Current of Compressor

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower gridCompressorCompressor wire
L2

Out-of-Step Failure of Compressor

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower gridCompressorSystem pressure
L3

Phase Failure of Compressor

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower gridCompressorCompressor wire
L4

Driver Module IPM Failure of Compressor

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower gridCompressor
L5

PFC Overcurrent Hardware Protection

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower grid
L6

PFC Overcurrent Software Protection

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower grid
L7

AD Abnormal Protection in Current Detection

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controller
L8

Shunt Resistance Imbalance Failure

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controller
L9

IPM Temperature Sensor Failure

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controller
LA

Compressor Startup Failure

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controllerPower gridCompressorCompressor wire
LC

AD Abnormal Protection in PFC Current Detection

Wall MountedFloor Standing DRAFT
See full procedure: F1

Subdivided failure of F1 (Module Protection Error). See F1 for the full diagnostic procedure.

Frequent Parts
Outdoor unit controller

Protection Codes

Protection

P1

Water Full Alarm

Mobile DRAFT

Three conditions can trigger this alarm: the water storage tank is full; the float switch has opened unexpectedly; or the main control panel is abnormal.

Inspection Path Water level in storage tank Float switch state Main control panel
Tools
Multimeter
Frequent Parts
Main control panelFloat switch
  1. Open the drain plug (located at the rear of the unit) and fully drain the water storage tank. Power off and restart to confirm normal operation.
  2. If the water level is normal, check the float switch. Confirm the float can move freely and return to its resting position. Use a multimeter to test whether the float switch closes properly in its normal (non-triggered) state. If the switch remains open, replace the float switch.
  3. If steps 1 and 2 do not identify the issue, replace the main control panel.
Special Attention: The most common cause is a full storage tank. The unit will restore normal operation automatically once the tank is drained.
P2

High-Voltage Switch Protection

Wall MountedFloor Standing DRAFT

The high-voltage switch has disconnected three times within 20 minutes, either in standby or during operation, triggering this protection.

Inspection Path High-voltage switch cable Connector High-voltage switch Main control panel
Tools
MultimeterReplacement connection lineReplacement high-voltage switch
Frequent Parts
High-voltage switch connection lineRefrigerant level (possible leakage)High-voltage switch
  1. Check that all plug-in terminals are firmly connected and that solder joints to the main control panel are not loose. Gently tug terminals if needed.
  2. Use a multimeter to check whether the high-voltage switch is currently disconnected.
  3. Use a multimeter to confirm the high-voltage switch is in the normally closed state under normal conditions.
  4. If system pressure is normal but the high-voltage switch remains open, the switch itself is faulty.
  5. If the pressure switch and connection line are both normal and the failure persists, replace the corresponding main control panel.
Special Attention: The most common cause of high-voltage switch disconnection is refrigerant leakage. Always verify system pressure first when this protection triggers. If pressure is normal but the error persists after replacing the main external control panel, the issue may be a connecting pipe that is too long or an external ambient temperature that is too low.
P3

Liquid Deficiency Protection

Wall MountedFloor Standing DRAFT

System refrigerant level has fallen below 30%, resulting in a loss of cooling capacity and liquid shortage protection.

Inspection Path Outdoor unit stop valves (confirm fully open) Evaporator, condenser, and connection pipes (check for damage or leaks) Environmental and coil temperature sensors (check both simultaneously)
Tools
Hex wrenchMultimeterPressure gauge
Frequent Parts
Stop valveEvaporatorCondenserConnection pipe
  1. Check the outdoor unit stop valves. Use a hex wrench to turn counterclockwise and confirm valves are fully open.
  2. Inspect the evaporator, condenser, and connection pipes for damage or cracks. Pay particular attention to weld points and pipe joints for refrigerant leakage.
  3. Use a multimeter to measure both the environmental temperature sensor and the coil temperature sensor at ambient temperature simultaneously. Abnormal resistance on both at the same time may suggest dual sensor failure rather than actual refrigerant loss.
P4

Refrigeration Overload Protection

Wall MountedFloor Standing DRAFT

The outdoor coil sensor is detecting excessive temperature. The system is actively reducing compressor frequency to prevent overloading.

LED Pattern ● ○ ●
Inspection Path Outdoor coil sensor resistance System pressure (check for dirty blockage) Outdoor fan speed Voltage dividing resistance in outdoor controller coil sensor circuit
Tools
MultimeterPressure gauge
Frequent Parts
Coil sensorCondenser (dirty)Outdoor fanOutdoor unit controller
Sensors Required
  • External coil (20 kΩ @ 25°C)
  1. Check the outdoor coil sensor with a multimeter. Standard resistance is 20KΩ at 25°C.
  2. Use a pressure gauge to check system pressure. High pressure may indicate dirty internal blockage or poor external heat transfer, both of which drive up coil temperature.
  3. Observe the outdoor fan speed. A slow-running fan reduces heat transfer and raises coil temperature.
  4. Use a multimeter to check the voltage-dividing resistance in the outdoor controller's coil sensor circuit. If uncertain, replace the outdoor controller and observe whether the protection clears.
P5

Exhaust Protection

Wall MountedFloor Standing DRAFT

The exhaust sensor has detected that exhaust temperature is too high, triggering a protection shutdown.

Inspection Path System pressure Indoor and outdoor air inlets Exhaust sensor External control panel
Tools
MultimeterPressure gauge50KΩ standard exhaust sensor (25°C)
Frequent Parts
System refrigerant levelIndoor and outdoor air inletsIndoor fan bladesExhaust sensor
Sensors Required
  • Exhaust (50 kΩ @ 25°C)
  1. Check system pressure. Low pressure typically indicates refrigerant shortage, which causes excessive exhaust temperature.
  2. Check that indoor and outdoor air inlets are unobstructed. Inspect for dirty evaporator or condenser coils, dirty filters, or blocked inlets — remove any shields if needed.
  3. Check indoor air volume at the supply vent. If indoor fan blades are dirty or blocked, clean them.
  4. Use a multimeter to measure exhaust sensor resistance at ambient temperature and confirm resistance drift is within normal range.
P6

Indoor High Temperature Protection

Wall MountedFloor Standing DRAFT

The indoor coil temperature has risen too high during heating mode, triggering a protection shutdown.

LED Pattern ○ ● ●
Inspection Path Indoor air inlet Indoor unit filter Indoor fan Indoor coil sensor
Tools
MultimeterPressure gauge
Frequent Parts
Indoor air inlet (blocked)Filter (dirty)Indoor fanIndoor coil sensor
Sensors Required
  • Internal coil (20 kΩ @ 25°C)
  1. Check that the indoor air inlet is unobstructed. Remove any shields or blockages affecting airflow.
  2. Check if the filter is dirty. Clean if clogged.
  3. Check indoor fan airflow at the supply vent. If the indoor fan is blocked or running slowly, clean it.
  4. Use a multimeter to measure the indoor coil sensor resistance at ambient temperature.
Special Attention: P6 typically indicates high temperature protection of the indoor heating coil caused by restricted air inlet.
P7

Anti-Freezing Protection in Refrigeration Mode

Wall MountedFloor Standing DRAFT

The indoor coil temperature has dropped too low during cooling mode, triggering a protection shutdown to prevent the heat exchanger from frosting.

LED Pattern ● ○ ○
Inspection Path Indoor air inlet Indoor unit filter Indoor fan Indoor coil sensor
Tools
MultimeterPressure gauge
Frequent Parts
Indoor coil sensorIndoor air inlet (blocked)Filter (dirty)Indoor fan
Sensors Required
  • Internal coil (20 kΩ @ 25°C)
  1. Check that the indoor air inlet is unobstructed. Remove any shields or blockages affecting airflow.
  2. Check if the filter is dirty. Clean if clogged.
  3. Check indoor fan airflow at the supply vent. If the indoor fan is blocked or running slowly, clean it.
  4. Use a multimeter to measure the indoor coil sensor resistance at ambient temperature.
Special Attention: P7 typically indicates anti-freezing protection of the indoor cooling coil caused by restricted air inlet.
P8

Overcurrent Protection

Wall MountedFloor Standing DRAFT

The controller has detected AC bus current exceeding the protection threshold and is limiting or reducing compressor frequency.

LED Pattern ○ ○ ★
Inspection Path Grid voltage (check for low voltage) System pressure (check for blockage) Outdoor unit controller
Tools
MultimeterPressure gauge
Frequent Parts
Grid voltageOutdoor unit controller
  1. Use a multimeter to check bus voltage. Low supply voltage is a common cause of overcurrent protection.
  2. Use a pressure gauge to check system pressure. Excessive pressure may indicate dirty blockage in the system.
  3. Replace the outdoor unit controller. If the unit returns to normal, the controller is faulty.
Special Attention: This protection typically occurs under high load conditions. It should not occur at low load or low ambient temperature. Protection priority is ranked after refrigeration overload (P4) and exhaust protection (P5).

Function Prompt Codes

Function Prompt

FP01

Compressor Overpower Protection

Wall MountedFloor Standing DRAFT

A function protection prompt — not a fault. Indicates the compressor is approaching its power limit and the system is actively reducing frequency to protect it. No alarm is displayed on the indoor unit. If this prompt occurs frequently, investigate supply voltage, module panel, and main external control panel.

LED Pattern ○ ● ★
Frequent Parts
Supply voltageModule panelMain external control panel
Special Attention: This entry has no standard indoor display code — it is identified by the outdoor unit LED pattern only (LED1 off, LED2 on, LED3 flash). Occasional occurrences under high load are normal.